EVIDENCE AND CASE STUDIES
Results and evidence by market
Choose your market to see documented results, project status and supporting evidence. Every project is labeled with its maturity, because completed evaluations, field demonstrations, pilots, shipments and commercial deployments are not the same thing.
Power generation results
Learn how THERMOPHASE is used in power generation →Commercial relationship Power generation is licensed to Pittsburgh Chemical Solutions (PCS) (opens in a new tab), which sells THERMOPHASE globally. Power-generation license with PCS since November 2022; license and exclusive distribution agreement with PCS and Nalco Water, 2026.
Plant results depend on cooling-water source, fouling regime and operating profile.

Longview Power
- Organization
- DOE Office of Fossil Energy · NETL
- Application
- Operating power-plant condenser
- Documented outcome
- 0.26 ± 0.13 inHg lower condenser back pressure; estimated $3.35M in fuel savings over two years

EPRI independent testing
- Organization
- Electric Power Research Institute
- Application
- Condenser-tube heat transfer
- Documented outcome
- Independent evaluation of heat-transfer performance
Industrial cooling results
Learn how THERMOPHASE is used in industrial cooling →Industrial cooling covers
- Building chillers
- District energy plants
- Chiller and heat-exchanger systems
- Data-center cooling
23.5%
Lower normalized condenser approach temperature, treated versus untreated 850-ton chiller
Navy hospital · reporting in progress
5.6–14.3%
Lower kW draw than four matched untreated ~2,000-ton chillers, by load range
New Orleans district energy plant · completed
0
New failed or degraded condenser tubes, 2021–2024, by eddy-current testing
Hospital facility · ongoing program
Economics differ by site, load and energy price; each documented result applies to the facility where it was measured.
Navy Hospital
- Organization
- DoD ESTCP · Navy hospital
- Application
- 850-ton facility chillers
- Documented outcome
- 23.5% lower normalized condenser approach temperature, treated versus untreated chiller
District energy plant, New Orleans
- Organization
- New Orleans, Louisiana
- Application
- Four ~2,000-ton centrifugal chillers versus four matched untreated controls
- Documented outcome
- 5.6–14.3% lower kW draw by load range; approach temperature maintained at 0.2–1.2 °F
Hospital facility
- Organization
- Pittsburgh, Pennsylvania
- Application
- Building chillers, treated annually since 2021
- Documented outcome
- Zero new failed or degraded condenser tubes 2021–2024 by eddy-current testing; annual tube cleaning avoided
Marine and seawater evidence
Learn how THERMOPHASE is used in marine and seawater systems →
USTS Kennedy
- Organization
- DOT Maritime Administration (MARAD), with Massachusetts Maritime Academy and Life Cycle Engineering
- Application
- Marine chiller and seawater cooling system
- Documented outcome
- Significant biofouling reduction after 115 days, 2021–2022
Marine is where THERMOPHASE began; current commercial availability is being defined.
Each card opens that demonstration’s full write-up, with its status, documentation and limitations.
HOW TO READ THE LABELS
Maturity labels
- Completed evaluation Independent or laboratory testing finished
- Completed field demonstration Operating-site demonstration finished
- Field demonstration · reporting in progress Demonstration done; final report pending