District energy plant, New Orleans
Four THERMOPHASE-treated centrifugal chillers of about 2,000 tons each, compared with four matched untreated chillers.
← All industrial cooling demonstrationsHow THERMOPHASE is used in industrial cooling →
Completed field demonstration
Demonstration summary
- Customer
- A district energy plant in New Orleans, Louisiana
- Application
- Water-cooled centrifugal chillers, about 2,000 tons each
- Status
- Completed
Result
5.6–14.3% lower kW draw than untreated chillers, depending on load: 7.9% at 25–50% load, 14.3% at 50–75% and 5.6% at 75–100%. Approach temperatures maintained at 0.2–1.2 °F.
Economic significance
Estimated $20,169 annual energy savings per treated chiller at the standard New Orleans rate of $0.098/kWh ($16,876 at a $0.082 commercial rate), calculated from measured kW draw, run time and load conditions
The problem
Condenser fouling raises chiller power draw and erodes heat transfer
What was done
Four chillers treated March 20–25, 2019; four matched chillers served as untreated controls. The customer confirmed clean condenser tubes on both groups before treatment, and historical performance was analyzed for each asset.
Limitations Loads below 25% were excluded as too variable. Sensor errors on two treated chillers and offline control chillers limited full analysis to the remaining assets. The 2019 protocol circulated THERMOPHASE for 6 to 18 hours per chiller; energy savings only, excluding maintenance.
Documentation
Case study with calculation table available on request →


MORE DEMONSTRATIONS
More industrial cooling demonstrations
Navy Hospital
- Organization
- DoD ESTCP · Navy hospital
- Application
- 850-ton facility chillers
- Documented outcome
- 23.5% lower normalized condenser approach temperature, treated versus untreated chiller
Hospital facility
- Organization
- Pittsburgh, Pennsylvania
- Application
- Building chillers, treated annually since 2021
- Documented outcome
- Zero new failed or degraded condenser tubes 2021–2024 by eddy-current testing; annual tube cleaning avoided