Industrial cooling

District energy plant, New Orleans

Four THERMOPHASE-treated centrifugal chillers of about 2,000 tons each, compared with four matched untreated chillers.

Completed field demonstration

Demonstration summary

Customer
A district energy plant in New Orleans, Louisiana
Application
Water-cooled centrifugal chillers, about 2,000 tons each
Status
Completed

Result

5.6–14.3% lower kW draw than untreated chillers, depending on load: 7.9% at 25–50% load, 14.3% at 50–75% and 5.6% at 75–100%. Approach temperatures maintained at 0.2–1.2 °F.

Economic significance

Estimated $20,169 annual energy savings per treated chiller at the standard New Orleans rate of $0.098/kWh ($16,876 at a $0.082 commercial rate), calculated from measured kW draw, run time and load conditions

The problem

Condenser fouling raises chiller power draw and erodes heat transfer

What was done

Four chillers treated March 20–25, 2019; four matched chillers served as untreated controls. The customer confirmed clean condenser tubes on both groups before treatment, and historical performance was analyzed for each asset.

Limitations Loads below 25% were excluded as too variable. Sensor errors on two treated chillers and offline control chillers limited full analysis to the remaining assets. The 2019 protocol circulated THERMOPHASE for 6 to 18 hours per chiller; energy savings only, excluding maintenance.

Bar chart of average chiller power draw across load ranges for treated and untreated chillers; treated chillers draw less power in the 25–50, 50–75 and 75–100 percent load ranges
Average power draw across load ranges, treated versus untreated chillers. Source: Biointerphase chiller case study.
Scatter plot of kilowatt draw against chiller load for treated and untreated chillers
Kilowatt draw per load, treated versus untreated chillers.

MORE DEMONSTRATIONS

More industrial cooling demonstrations

Field demonstration · reporting in progressIndustrial cooling

Navy Hospital

Organization
DoD ESTCP · Navy hospital
Application
850-ton facility chillers
Documented outcome
23.5% lower normalized condenser approach temperature, treated versus untreated chiller
Demonstration details: Navy Hospital →
Ongoing programIndustrial cooling

Hospital facility

Organization
Pittsburgh, Pennsylvania
Application
Building chillers, treated annually since 2021
Documented outcome
Zero new failed or degraded condenser tubes 2021–2024 by eddy-current testing; annual tube cleaning avoided
Demonstration details: Hospital facility →